BMS-100 Controller

Burner Management for Flares, ECD and Firetube Applications

The BMS-100 is a pilot maintainer with secondary valve control. It auto-ignites and relights pilot burners associated with Flares, ECD / Combustors or naturally drafted burner applications. This system ensures the standing pilot remains lit 24/7 to ensure combustion of a main burner when necessary.

Applications

Suitable for Flares, ECD / Combustors, or Naturally Aspirated Industrial Burners Rated up to 10 million Btu/h.

 

Specifications Manual Data Sheet

 

Specifications – BMS-100 Controller

Applications
  • Suitable for Flares, ECD/Combustors, or Naturally Aspirated Industrial Burners Rated up to 10 million Btu/h.
Features
  • Easy Startup Sequence
  • Auto-Ignition and Auto Relight Sequencing
  • LED Display Screen
  • LED Indication
  • Adjustable Pre-purge Timing
Compatible Components
  • FT Ignition Unit
  • Solenoid Valves
  • Actuator Valves
  • Pressure Switches
  • Pressure Transducers
  • Thermocouples
Shutdown Features
  • Ignition Failure
  • Flame Sense Failure
  • Igniter Failure
  • Thermocouple Failure
  • 2 Shutdown Interlocks
Inputs / Outputs
  • Run Status
  • Alarm Output
  • 2 Standby Interlocks
  • 2 Shutdown Interlocks
  • Remote On
  • Remote Off
  • 4-20mA Input for Combustor Applications
Enclosure
  • Polycarbonate Enclosure rated @ NEMA 4X meets IP66 criteria
  • UL Listed
  • UV Resistant Keypad

 

System Feedback
  • System On
  • System Off
  • Battery Voltage
  • Status Code
  • Flame Sensing Value
  • Safety Thermocouple Value
  • Pressure Signal
  • Audible Ignition Indicator
Optional Adder Card Features
  • 4-20mA Input for Combustor Application
  • Data Logging Pilot Flame
  • Additional Thermocouple Shutdown
  • Modbus RS-485 Communication Protocol
Operating Specifications
  • Battery Voltage: 11-15 VDC
  • Solar Panel Voltage: 12 VDC
  • Solar Panel Current: 8 amps max
  • Igniter Amps: 6.5 amps inrush, 2 amps nominal (during the ignition sequence)
  • System Current Draw: 0.6 amps average
  • Ambient Temperature -40°F / +130°F
Warranty
  • Three Year Warranty Policy
Certifications
  • CLASS 1 DIV 2 Groups C, D, & T6
  • CAN/CSA-C22.2 No. 213-7
  • UL 121201 (Ed9) & ANSI Z21.20-2014/CAN/CSA-C22.2 No 60730-2-5-14
  • UL STD 61010-1&UL STD 61010-2-030
  • UL STD 121201:2017 ED.9